The zone module permits the addressable FACP to interface and monitor 2-wire /4-wire conventional smoke detectors and manual call point. The address of each module is selected by using DIP switch and it utilizes a single address to communicate with Addressable FACP. It transmits the status (Alarm / Normal / Open / Short / 24V fault) of one zone of 2-wire / 4-wire detectors to the FACP. Zone module supervises the zone of detectors and the connection of the external power supply, respectively. The red blinking LED indicates normal operating condition and the steady state for activated condition.

The panel status shall be visually indicated in unambiguous color with distinguished inbuilt audible tone. This system can operate as a standalone or connect to 16 network nodes with network interface card

  • UL Listed 864 10th edition.
  • Supervised 24V Input & Resettable 24V output
  • Supervised Class B Initiating Device Circuits.
  • Status LED.
  • 2 / 4 wire conventional detector interface facility.
  • DIP switch for addressing.
  • Address between 1 – 250.
  • SLC communication with the panel.
  • Single gang box.
  • Electrical Specifications
    SLC Operating Voltage 24 VDC Nominal
    SLC Alarm Current
    3 mA (max) Latched
    SLC Standby Current 0.5 mA
    End of Line Resistor 47K ½ watt
    IDC Wiring resistance 40 Ω Max (20 Ω each side)
    IDC Standby current 1 mA
    IDC wiring Style Class B
    External Supply Voltage 17 – 32VDC
    External Alarm Current 50 mA (max)
    External Standby Current 15 mA (max)
    Temperature Range 0 – 49° C / 32 – 120° F
    Storage Temperature 0 – 60° C / 32 – 140° F
    Humidity 93 ± 2% RH (non-condensing)
    Mechanical Specification
    IP rating IP 40
    Dimensions (76.6L X 71.6W X 22D) mm (without gang holder)
    (125.5L X 85.5W X 22.2D) mm (with gang holder)
    Material FRABS
    Weight 80 g

    ADDRESSABLE ZONE INTERFACE MODULE

    Download Datasheet.

    ...