This addressable smoke detector can be installed on any side of the duct. The detector RE-428DU-S contains an intelligent controlling circuit. The circuit adjusts the sensitivity to give an optimal function throughout the entire life of the detector. Advanced Venturi tube technology with single tube detector. This duct detector housed with the flow optimization and two feet sampling pipe.
Electrical Specifications | |||
---|---|---|---|
Operating Voltage | 17 ~ 28V DC | Operating Temperature | -10 – 37.8° C | Storage Temperature | -10 – 60° C | Humidity | 0 - 95% RH, non-condensing | Reset Voltage | Less than 3V | Standby Current | 500 µA | Alarm Current | 5 mA | Startup Time | 30 sec C (138 o F). | Remote Ouput | 2mA maximum open collector | Smoke Sensitivity | (2.12 ± 0.61) % obs/ ft. (High: 1.1; Medium: 1.4; Low: 2.3)% obs/ft | Air Velocity | 0 – 4000 fpm | Dimensions | (241 L X 195 W X 68 D) mm | Weight | 1.20 kg |