The Loop Card is compatible for Aaral X4(4 loop panel) & Aaral X8(8 loop panel). Up to 250 devices can be connected in a single loop card. Loop Card is compatible with addressable detectors (heat, smoke & multi), initiating devices (Pull station, Monitor module, Zone module, etc.,), output device (Control, Relay, Sounders & Sounder - Strobe, etc.,).


  • Loop wise device test .
  • Loop card can programmable as Class A, Class B and Class X wiring.
  • Maximum 250 devices per loop.
  • Auto learning facility.
  • Electrical Specifications
    Number of Devices per loop 250
    Loop resistance 40 ohms (Max.)
    Loop capacitance 0.6 μf (Max.)
    Loop Current 350mA (Max.)
    Operating Temperature 0 - 49° C / 32-120° F
    Relative Humidity 93 ± 2% RH (non-condensing) at 32 ±2° C / 90 ±3° F

    LOOP CARD FOR AARAL

    Download Datasheet.

    ...