The Input Output module is intended for the use in intelligent two wire system with inbuilt isolator. The address of each module is selected by using the DIP switch and it utilises 2 consecutive addresses from the set address. This module automatically assigns the first address as input and consecutive address as output. This module contains one form C relay contact allowing the panel to switch the contacts on command and one electrically supervised input to monitor flow switches, pull stations, sprinkler valves, fire dampers etc. It also supervises the wiring connected and reports their status to the panel as (Alarm / Normal / Open). The red blinking LED indicates normal operating condition and the steady state for activated condition.

The panel status shall be visually indicated in unambiguous color with distinguished inbuilt audible tone. This system can operate as a standalone or connect to 16 network nodes with network interface card

  • UL listed 864 10th edition.
  • Supervised contact monitoring circuits.
  • 1 Form C, Potential Free Contact.
  • Status LED.
  • DIP switch for addressing.
  • Address between 1 – 249.
  • Inbuilt isolator.
  • SLC communication with the panel.
  • Single gang box.
  • Electrical Specifications
    Operating Voltage 24 VDC Nominal
    Alarm Current
    2.7 mA (max)
    Standby Current 0.7 mA
    End of Line Resistor 47K ½ watt
    Wiring Resistance 100 Ohms (max)
    Wiring Style Class B
    Contact Rating 2 A @ 30 VDC (resistive)
    Contact Type Form C (Potential Free Contact)
    Temperature Range 0 – 49° C / 32 – 120° F
    Storage Temperature 0 – 60° C / 32 – 140° F
    Humidity 93 ± 2% RH (non-condensing)
    Mechanical Specification
    IP rating IP 40
    Dimensions (76.6L X 71.6W X 22D) mm (without gang holder)
    (125.5L X 85.5W X 22.2D) mm (with gang holder)
    Material FRABS
    Weight 80 g

    ADDRESSABLE INPUT OUTPUT MODULE

    Download Datasheet.

    ...