Addressable heat detector(s) are designed to work with Addressable Fire Alarm Control Panel. These detectors are low profile, polarity free and have dual LED’s for 360° visual indication. The LED’s are blinking in normal operating condition whereas the LED's in steady state indicate alarm status. Addressable heat detector is a fixed cum rate of rise heat detector using a thermistor. These detectors will raise an alarm when the detector reaches 59°C (Fixed) or when the change in temperature exceeds the rate of rise of 11°C / min.


  • UL listed and NFPA standard.
  • Polarity free, Dual LED’s, and 360°visibility.
  • Insect Filter.
  • Fixed temperaure and rate of rise detection.
  • Advanced detection and communication protocol.
  • Easy to install.
  • Sleek low-profile housing design
  • Regular 100mmbase.
  • Address set by 8 digit DIP switch.
  • Electrical Specifications
    Operating Voltage 17 ~ 28V DC
    Reset Voltage Less than 3V.
    Standby Current 500 µA.
    Start up Time 30 sec.
    Alarm Current 5 mA .
    Remote Output 2mA maximum open collector
    Detector Spacing 9 meters.
    Fixed Temperature 59o C (138 o F).
    Rate of Rise of Temperature 11.1 o C / min (20 o F/min).
    Operating Temperature -10o C to 37.8o C.
    Storage Temperature -10 o C to 60 o C.
    Humidity 0 – 95% RH, non-condensing
    Mechanical Specification
    Dimension 46 H x 100 D (mm)
    Weight 150 g with base
    Material FR ABS plastic
    IP Rating IP-42

    ADDRESSABLE HEAT DETECTOR

    Download Datasheet.

    ...
    ...


  • UL listed and NFPA standard.
  • Polarity free, Dual LED’s, and 360°visibility.
  • Insect Filter.
  • Fixed temperaure and rate of rise detection.
  • Advanced detection and communication protocol.
  • Sleek low-profile housing design.
  • Fixed temperaure and rate of rise detection.
  • Regular 100mmbase.
  • Advanced detection and communication protocol.
  • Address set by 8 digit DIP switch.
  • Electrical Specifications
    Operating Voltage 17 ~ 28V DC
    Reset Voltage Less than 3V.
    Standby Current 500 µA.
    Start up Time 30 sec.
    Alarm Current 5 mA .
    Remote Output 2mA maximum open collector
    Smoke Sensitivity (2.12 ± 0.61) % obs/ ft (High: 1.1% obs/ft; Medium: 1.4% obs/ft; Low: 2.3% obs/ ft).
    Air Velocity 0 – 4000 fpm.
    Detector Spacing 9 meters
    Operating Temperature -10o C to 37.8o C.
    Storage Temperature -10 o C to 60 o C.
    Humidity 0 – 95% RH, non-condensing
    Mechanical Specification
    Dimension 46 H x 100 D (mm)
    Weight 150 g with base
    Material FR ABS plastic
    IP Rating IP-42

    ADDRESSABLE MULTI SENSOR DETECTOR

    Download Datasheet.

    ...