The Voice Alarm Panel RE-2AS RVAP is designed to provide with evacuation system controls for different areas. It allows to know the condition of the system and broadcast both live and pre-recorded alarm and evacuation warnings through up to 56 selection memories of evacuation zones.

This is possible because it can equipup to 7 expansion keyboards with 8 zone memories each one. Moreover, expansion keyboards available allow it to adjust to the special features of each system

The equipment also offers the chance to choose the source of the power supply between local or supplied through the ACSI bus. The ACSI bus allows a maximum total wiring of 1000m (914.4 yrd) and offers priority levels for the devices connected in bus mode

It has functions such as volume control, dynamic sound adjustment and programmable buttons that allow other system functions such as pre-recorded messages broadcasting.

It has a metallic chassis that provides stability and protection against damage. All the buttons are designed for instensive use.


  • Up to 56 group memories of up to 8 zones per memory (448 zones of the system)
  • Prior notice tone.
  • Volume adjustment.
  • Power supply indicator.
  • Emergency condition general indicator.
  • Fault condition general indicator.
  • Link with system fault indicator.
  • Power supply fault indicator.
  • Emergency microphone fault indicator
  • Broadcasting of voice evacuation message indicato
  • Broadcasting of voice evacuation recorded message indicator.
  • Broadcasting of voice alarm message indicator.
  • Remote control indicator.
  • Emergency controls, Reset, Acknowledge, Test, Alarm message, Evacuation message.
  • Side port to connect up to 7 expansion keyboards.
  • Priority configuration and operating parameters.
  • Priority configuration and operating parameters.
  • Electrical Specifications
    Power supply 4.5 - 5.5V DC, 1 x mini USB AB
    RE-2AS RVAP power consumption 200 - 500 mA (max with all the expansion keyboards)
    Expansion keyboard consumption 40 mA max
    Frequency response 200 Hz – 12000 Hz (+/- 2dB)
    Signal to noise ratio > 98dB, A-weighted
    Sensitivity - 43 dB (1KHz)
    Directionality Axial, with hypercardioid type polar diagram
    Type of transducer Dynamic with moving coil
    DSP Integrated. 48 kHz, 24 bits – 172 MIPS
    ACSI Bus 2 x Balanced Audio (In+Loop)1Vp, 0,707Vrms. 10 KΩ, 2 x RJ-45 Female, Total 1000m. / 3280,84ft
    Expansion Port 1 x Pin row, 2 rows x 5 female contacts
    Indicators (W x H x D) Condition: Emergency, General Fault, Remote Control Fault: Link, Supply, Emergency microphone Messaje in broadcast: Evacuacion recorded, Warning recorded, live message
    Buttons Emergency, Reset, Confirmation, (EMG, RST, ACK) 1 button for talking (TALK) Recorded message: Evacuation and Warning Indicators test
    Functions Prior notice tone, volume control, DSA (Dynamic sound adjuster). Directionality until 448 system zones.
    Microphone cable length 500mm / 13,75”
    Dimensions without microphone (A x H x P) 259mm x 132mm x 50mm / 3,38” x 2,56” x 7,48”
    Dimensions with microphone (A x H x P) 259mm x 132mm x 93mm / 3,38” x 2,56” x 7,48"
    Keyboard/Rack complements dimensions (A x H x P) 86mm x 132mm x 42mm / 3,38” x 2,56” x 7,48”
    Operating conditions 5°C to +45°C / 23°F to 113°F 5% to 95% Relative Humidity (no condensation)
    Finish Fe, Grey RAL 7016
    Weight 1 Kg / XX,x lb
    Expansion keyboard weight 0.5 Kg / XX,x lb
    RE-2AS RVAP accesories 1 x miniUSB AB male to USB A male 1x Power Supply USB connector Type C (EU Type) 1 x Ethernet cable 2m / 6,56ft. 2 x 19” Rack installation accessories 1 x block accessory for wall instalation
    Expansion keyboard accesories 1 x expansion port adaptor 2 x 5 contacts male-male 1 x connecting piece to VAP 1 4 x countersunk screw (4 x 8 mm)